2 GW of deployment, 1 GWh production line in pilot operation vs. 647 systems down: Zinc‑air batteries are reshaping the fundamental power‑backup logic of data centers in the AI era!
Release time:
2026-10-14
In 2025, a 22-hour fire at the Daejeon data center in South Korea disabled 647 systems, once again bringing lithium‑battery backup power safety to the forefront. As AI computing demand surges, intrinsic‑safety zinc‑based battery technology is accelerating the reshaping of the fundamental technological framework for data‑center backup power.
I. A lithium‑ion battery explosion has sounded the alarm about data center safety hazards.
On the evening of September 26, 2025, a sudden fire broke out on the fifth floor of the data center at the National Information Resources Management Institute in Daejeon, South Korea. According to the subsequent investigation, the immediate cause was the unexpected explosion and ignition of a ternary lithium-ion battery that had been in use for more than 12 years, during an electrical‑power‑off relocation process.
⚠️ Accident Loss Statistics
- The fire raged on for a full… 22 hours
- 647 government business systems have completely collapsed.
- 96 systems were completely destroyed and cannot be recovered.
- A large number of public services have been disrupted, resulting in significant social repercussions and economic losses.
This is far from an isolated incident. In recent years, lithium‑battery fires at data centers have occurred with alarming frequency worldwide: the risk of thermal runaway steadily accumulates as batteries age, and such incidents are particularly likely to be triggered under conditions like power outages, handling operations, or extreme temperatures. The high energy density of ternary lithium batteries further exacerbates these risks, in… Today, as demand for AI computing power surges, it is becoming a “Sword of Damocles” hanging over data centers.
When AI computing power is expanding at a rate of doubling each year, and data centers’ reliance on reliable power supplies has reached an unprecedented level. Yet the battery systems that serve as the final line of defense for these “computing power hubs” are increasingly emerging as a critical risk factor. A quiet wave of technological substitution in the battery space is already beginning to unfold.
II. Upgrading Backup Power Needs in the AI Era: Traditional Backup Power Solutions Face Numerous Challenges
To understand this wave of substitution, one must first grasp The fundamental differences in power consumption logic between AI data centers and general-purpose data centers.
The workload of traditional data centers is primarily CPU servers dominate, with power fluctuations relatively mild. In contrast, the core workload of AI data centers is GPU clusters— With NVIDIA AI accelerator cards such as the H100 can consume up to 700 watts per card, enabling a standard rack to easily exceed a power density of 30 kilowatts—or even higher. This means that when the utility power experiences millisecond-level fluctuations, The load fluctuations in AI data centers are far more pronounced than in traditional scenarios.
The UPS system plays a highly specialized role in this context. Its core function is not to provide long‑term power supply, but rather to rapidly deliver stored energy during brief power‑grid anomalies, momentary outages, or the transition between primary and backup power sources, thereby supporting servers, Ensure uninterrupted power supply for critical workloads such as GPU clusters, while minimizing the time required for diesel generators to start up and synchronize with the grid. — Usually only 5 to 15 minutes.
This time window determines The key performance metrics for UPS batteries are not energy density, but rather power density and response speed. The battery must deliver high‑current discharge at the instant of a power outage while maintaining absolute reliability.
Comparison of the Core Differences in Power Consumption Logic Between AI Data Centers and General-Purpose Data Centers:
| Comparison dimension |
General-Purpose Data Center |
AI Data Center |
| Core Load Type |
With CPU servers are the primary focus. |
With NVIDIA GPU clusters such as the H100 serve as the core workload. |
| Power density per cabinet |
Usually 5–10 kW per cabinet |
Easily break through 30 kW per cabinet; in high-density scenarios, it can reach 40–100 kW per cabinet. |
| Load Fluctuation Characteristics |
Power fluctuations are smooth, with no abrupt transients. |
Millisecond-level dramatic fluctuations, Within 10 ms, the load can surge from 30% to 150%. |
| Mains Voltage Fluctuation Tolerance |
Low sensitivity to millisecond-level utility power fluctuations. |
The load varies dramatically, placing extremely stringent demands on the stability of instantaneous power supply. |
| UPS Core Positioning |
Balancing short-term transition and basic backup power supply |
The mains power anomaly window enables millisecond‑level rapid discharge, buying time only for the diesel generator. 5–15 minutes for startup and grid connection time |
| Core Performance Requirements for Batteries |
Prioritize energy density and cycle life. |
Priority assurance Power density With millisecond-level response speed, it can deliver stable high-current discharge the instant power is lost. |
That’s precisely where the problem lies. Currently, approximately 90 percent of the world’s… UPS backup systems still rely on lead-acid batteries. According to a report by Vertiv, 55% of unplanned data center outages and one-third of UPS system failures are attributable to valve-regulated lead-acid battery failures. Lead-acid batteries have a low power density, so to meet transient power demands, operators are forced to install battery banks that far exceed actual requirements. —This not only drives up costs and floor space requirements but also increases maintenance complexity.
Lithium‑ion batteries appear to be an upgraded option; industry reports forecast that by 2026, their penetration in data center UPS systems will exceed 47%, as they displace lead‑acid batteries and become the mainstream choice for new projects. The energy density of lithium iron phosphate batteries is that of lead-acid batteries. Its energy density is 3 to 4 times higher, and its cycle life is 6 to 8 times longer; under the same backup‑power requirements, it can reduce the footprint by two‑thirds. However, the safety risks of lithium batteries are amplified in high‑density data center environments. In the Daejeon incident in South Korea, a ternary lithium battery, after thermal runaway, rapidly triggered a chain reaction: the electrolyte ignited, the fire spread, and firefighters were unable to employ aggressive firefighting measures. For data centers hosting critical government, financial, and healthcare systems, such risks are unacceptable.
► Lithium‑battery backup power solutions face three intractable challenges:
① The inherent trade-off between safety and energy density
The higher the energy density of a lithium battery, the greater the risk of thermal runaway. Using more than… After eight years, issues such as separator aging and electrolyte decomposition can significantly increase the risk of thermal runaway. Meanwhile, AI‑driven data centers typically require battery backup systems with a design life exceeding ten years, creating an inherent mismatch between safety margins and longevity requirements.
② High full lifecycle cost
Lithium batteries require complex… BMS battery management systems, thermal‑management cooling systems, and fire‑suppression systems require capacity testing and partial replacement every 3 to 5 years; over a 10‑year period, total operation and maintenance costs can amount to 2–3 times the initial procurement cost.
③ Concentration of fire risks in large-scale deployments
In AI data centers, the backup power capacity of a single campus has reached the hundred‑MWh or even GWh level, with thousands or tens of thousands of lithium batteries densely deployed. Should a single cell experience thermal runaway, it can easily trigger a cascading chain reaction, and conventional gaseous fire‑suppression systems struggle to prevent re‑ignition at the cell level.
The industry is currently urgently seeking ways to… Simultaneously satisfy Three core requirements: absolute safety, ultra-high power density, and millisecond-level rapid response. The next-generation backup power technology roadmap thoroughly addresses the shortcomings of traditional lead-acid and lithium batteries in… Inherent limitations in AI‑driven high‑density computing scenarios.
III. What strengths enable zinc batteries to secure a spot in AIDC’s backup power market?
Zinc batteries are not a new technology. The nominal voltage of nickel–zinc batteries is 1.6 volts, with an energy density of 60 to 100 Wh/kg, operates over a wide temperature range from −40°C to 50°C, and can deliver high‑rate discharges at up to 10C. However, due to its significantly lower energy density compared with lithium batteries, zinc‑air batteries have long remained on the fringes of the battery race dominated by new‑energy vehicles.
The rise of AI‑driven data centers has, quite by chance, opened a previously unexplored door for zinc batteries. Compared with conventional lithium‑ion batteries, zinc batteries offer three fundamental advantages in data‑center backup‑power applications:
✅ Intrinsic safety is the core differentiator.
Zinc batteries use an aqueous electrolyte and contain no flammable or explosive organic solvents, thereby eliminating the risk of thermal runaway at the material‑system level. Under extreme conditions such as needle puncture, compression, overcharging, and short circuit, they neither ignite nor explode, ensuring intrinsic safety even in high‑risk scenarios like handling aged batteries or performing maintenance during power outages.
✅ High-rate discharge saves space.
The high-rate discharge capability of zinc batteries is a perfect match. The core requirement of UPS systems for “instantaneous high-current discharge.” Zinc batteries possess 10C high magnification It boasts excellent discharge performance, delivering a stable and safe high‑current output even at the moment of power failure. In terms of space and weight, for the same power output, its volume and mass are only one‑third those of a lead‑acid battery.
✅ Wide operating temperature range and long service life significantly reduce the total lifecycle cost.
Zinc batteries can operate reliably in ambient temperatures ranging from –20°C to 60°C, eliminating the need for complex temperature‑controlled air‑conditioning systems and significantly reducing data center energy consumption for thermal management as well as associated infrastructure costs. The cycle life of zinc batteries can reach 6,000 to 10,000 cycles, with a float‑charge lifespan… Accessible 15–20 years, aligned with the service life of data center buildings, eliminating the need for battery replacement over the entire lifecycle and significantly reducing operation and maintenance costs and… Retirement disposal pressure.
Intrinsic safety, high power density, and low cost over the entire lifecycle — With all three conditions met, zinc batteries have carved out a precise niche in AIDC backup power applications, positioning themselves between lithium‑ion and lead‑acid batteries.
IV. 2 GW of Deployment and 1 GWh of Pilot Production: Zinc Batteries Have Achieved a Critical Leap Toward Industrialization in the AIDC Backup Power Market
In the face of the inherent limitations of lithium batteries, zinc‑based battery technology is accelerating its commercial deployment worldwide. According to publicly available industry data, the global installed capacity of zinc‑battery energy storage systems has already reached 2 GW; a 1 GWh domestic zinc‑battery production line has entered the pilot‑production phase.
Global leader in nickel-zinc batteries ZincFive’s progress provides a key benchmark. In December 2025, ZincFive closed an oversubscribed Series F round of $30 million, with its nickel‑zinc backup power solutions already deployed across global data centers and contracted capacity approaching 2 GW. Just four months later, in April 2026, the company announced that this scale… Official breakthrough 2GW。 Its The BC-series AI battery cabinet is specifically designed for high‑power, dynamic load scenarios in AI data centers. Additionally, a nickel–zinc retrofit kit enables operators to upgrade existing lead‑acid systems to nickel–zinc batteries on-site, without replacing the cabinet.
From a technical perspective, aqueous zinc batteries and nickel–zinc batteries are… AIDC’s backup‑power solutions each have their own focus. Nickel–zinc batteries offer higher specific energy, making them well suited for applications with stringent requirements on backup‑power duration, while aqueous zinc batteries boast superior safety and excel in high‑power, short‑duration discharge scenarios. These two approaches are not mutually exclusive; rather, they complement one another by addressing distinct niche needs.
As the industry outlook continues to brighten, zinc batteries are moving toward large-scale commercialization. The “last mile” still needs to overcome several critical bottlenecks.
Cycling stability of the zinc anode
During repeated charge–discharge cycles, the zinc anode surface is prone to side reactions such as dendrite growth, hydrogen evolution, and self‑corrosion, which directly limit the battery’s cycle life and Coulombic efficiency. To address these challenges, the industry has undertaken technological research and development in areas including the formation of artificial protective layers, membrane modification, and optimization of electrolyte formulations. Currently, mainstream nickel–zinc batteries can achieve a cycle life of up to 400–500 cycles; some iteratively improved models have already surpassed 1,200 cycles, yet there remains room for improvement compared with the several thousand cycles typical of conventional lead‑acid batteries.
The industry standards system remains to be improved.
In data center backup power applications, battery reliability is subject to nearly stringent requirements, and products must pass… UL, IEC, and a series of other international safety certifications; at present, the development of standards for zinc batteries in this field remains in its early stages. Leading companies such as Senke Chuangneng have already taken the lead in participating. The development of relevant standards, such as “Zinc–Nickel Battery Packs for Industrial Equipment” and “Zinc–Nickel Batteries for Emergency Power Supplies,” is driving the industry’s transition from a fragmented product‑validation phase to a systematic, standardized stage.
The ramp-up of production capacity and the cost curve have not yet achieved a positive alignment.
Although the 1 GWh production line has achieved a phased breakthrough, given the global data center UPS market’s existing size of approximately US$7.7 billion in 2025 and an anticipated growth to US$15.5 billion by 2033, the industry as a whole still faces a significant capacity gap. Before the full realization of economies of scale, whether the cost advantage of zinc batteries can be sustained hinges critically on the pace of subsequent capacity expansion and the extent to which production yields improve.
Overall, zinc batteries are in The commercialization window for AIDC backup power has officially opened. As technological advancements continue to advance, the standards framework gradually matures, and production capacity expands, this high‑safety energy‑storage technology is poised to become a key pillar of the backup power systems for future intelligent computing centers.
V. State Policy Orientation for the 15th Five-Year Plan: Intrinsic Safety and Diversified Technological Pathways Emerge as Core Priorities
The commercialization of zinc-based battery technology, together with the nation… During the 15th Five-Year Plan period, the top-level design for the next-generation battery industry aligns closely with energy storage safety. Since 2026, multiple departments, including the Ministry of Industry and Information Technology and the National Energy Administration, have successively issued specialized plans, outlining the development roadmap for the energy storage battery industry over the next five years:
Development of the New-Type Battery Industry The 15th Five-Year Plan (MIIT Joint Regulation [2026] No. 220)
This is the first national five-year special plan in China’s battery sector, jointly formulated by the Ministry of Industry and Information Technology and six other departments. Jointly issued in September 2026, the Plan explicitly sets forth the core principle of “coordinating development and security,” establishes a new battery supply system characterized by lithium‑based batteries as the mainstay, with sodium‑ion and flow batteries developing in tandem, and designates “safety and efficiency” as the central objective of the emerging battery industry. Furthermore, in the product‑innovation section, it explicitly calls for “enhancing the power density and cycle life of iron‑based and zinc‑based flow batteries,” positioning zinc‑based batteries as a key priority within the portfolio of next‑generation battery technologies.
In terms of application scenario deployment, the Plan explicitly states that by… By 2030, new battery technologies will need to be further deployed in energy storage applications such as industrial parks and data centers, with a particular focus on advancing their use in intelligent computing center settings.
Electric Power Safety Production “15th Five-Year Plan” Action Plan
National Energy Administration Issued in August 2026, the document sets forth specific requirements for the safety of next-generation energy storage: “Improve the comprehensive, end-to-end safety standards system and safety assessment mechanisms, and strengthen safety oversight and information sharing for new energy storage technologies,” thereby advancing a shift in power‑sector safety governance toward proactive prevention. With technology at its core, it promotes intrinsic safety measures and, at the regulatory level, establishes clear safety red lines for energy storage systems in critical applications such as data centers.
Construction of a New Energy System The 15th Five-Year Plan
The National Development and Reform Commission and the National Energy Administration jointly issued a document, setting out specific quantitative development targets: by By 2030, the nationwide installed capacity of new‑type energy storage will reach 300 million kilowatts. The industry will officially transition from a policy‑driven model that mandates energy‑storage deployment to a new, market‑oriented phase, with energy‑storage technologies characterized by intrinsic safety, long service life, and low operation‑and‑maintenance costs poised to capture greater market share.
In In today’s era of rapid deployment of AI computing infrastructure, the safety of backup power systems is an inviolable bottom line. Zinc batteries are emerging from obscurity. “An alternative option” has become an indispensable “must-have” within the backup power system. From lithium batteries to zinc batteries, this represents not only an evolution of the material systems but also a shift in the design philosophy of backup power systems from… The fundamental shift from “post‑incident fire protection” to “intrinsic safety” is highly aligned with the national development direction for the new‑generation battery industry during the 15th Five‑Year Plan period.
From a global perspective of practical applications, zinc batteries have already been deployed in backup power systems for telecommunications base stations and data centers. Scalable validation has been achieved in applications such as UPS systems and commercial‑industrial energy storage. As the development of AI‑driven computing infrastructure accelerates, and in line with the national “15th Five-Year Plan” policy that explicitly promotes intrinsically safe energy‑storage technologies, zinc‑based batteries—characterized by intrinsic safety, long cycle life, and low operation‑and‑maintenance costs—are emerging as one of the mainstream options for data‑center backup power.
-------------------------------------------------------------------
Source of information:
1. The key events and data presented in this article are drawn from “2 GW Deployed, 647 Systems Down, 1 GWh Line in Trial Production: Zinc Batteries Are Reshaping the Underlying Logic of Backup Power for AI Data Centers!”
2. The policy content is drawn from the official public documents, including the “15th–16th Five-Year Plan for the Development of the New‑Type Battery Industry” issued by the Ministry of Industry and Information Technology and six other departments (MIIT Joint Regulation [2026] No. 220), the National Energy Administration’s “15th–16th Five-Year Action Plan for Power Safety Production,” and the National Development and Reform Commission and the National Energy Administration’s “15th–16th Five-Year Plan for Building a New‑Type Energy System.”